Boiler size calculator
Work out the boiler size your home needs from the gas you already use and the shower you already have, not from counting radiators.
On your annual statement or your supplier’s app. Not sure? Use a typical figure:
To measure it, hold a bucket under the shower on full for 10 seconds, then multiply the litres by 6.
Adjust the assumptions
A typical household’s, by the government’s SAP method. If you know your summer gas use, a summer day’s gas × 365 is a good figure.
The share of the gas that ends up as heat over a year.
Heating, coldest days
2.2 kW
At -3°C outside, as cold as it gets near London Heathrow in all but a few hours a year, heating the way you do now.
Hot water, one shower
29 kW
To heat 12 litres a minute by 35°C, from cold winter mains water to a hot shower.
A combi of about 30 kW covers you. Hot water decides the size: any combi has far more than the 2.2 kW your heating needs. A smaller one still works, but the shower runs cooler or slower in winter.
Even on the coldest days your heating needs less than many combis can turn down to (5.2 to 6.1 kW on the models we checked). On milder days a boiler like that switches on and off rather than ticking over, which wastes a little gas. If you’re replacing a boiler, ask for one with a low minimum output, and turn the flow temperature down either way.
| Hot water output | Litres a minute at 35°C rise | Your showers |
|---|---|---|
| 24 kW | 9.8 | Runs short |
| 28 kW | 11.5 | Runs short |
| 30 kW | 12.3 | Keeps up |
| 35 kW | 14.3 | Keeps up |
Your home loses about 119 watts for every degree colder it is outside, worked out from 6,460 kWh of heat a year and 2,255 degree days. Heating that goes off overnight needs extra output to warm the house in the morning, which a combi has plenty of. An installer should still check before fitting a boiler.